vibration transmitter (for use w/icp® sensor), 4 to 20 ma output, 10  to 1k hz

IN-LINE ICP TO 4-20 MA OUTPUT VELOCITY CONVERTER

Model 682A09

  • IP

Vibration transmitter (for use w/ICP® sensor), 4 to 20 mA output, 10 to 1k Hz

  • Output Range: 4 to 20 mA (4 to 20 mA)
  • Frequency Response: (-3dB ±2dB)600 to 60000 cpm (10 to 1000 Hz)

Specification Notes


English: SI:
Performance
Input Signal (ICP Accelerometer) 100 mV/g 10.2 mV/(m/s²)
Frequency Response (-3dB ±2dB ) 600 to 60000 cpm 10 to 1000 Hz
Measurement Range 0.0 to 1.0 in/sec pk 0.0 to 25.4 mm/s pk
Output Range 4 to 20 mA 4 to 20 mA
Broadband Resolution 0.01 in/sec pk 0.26 mm/s pk
Environmental
Temperature Range -40 to 185 °F -40 to 85 °C
Temperature Response (Sensitivity Deviation) ≤15 % ≤15 %
Electrical
Excitation Voltage 20 to 30 VDC 20 to 30 VDC
Electrical Isolation (Case) >100000000 Ohm >100000000 Ohm
Settling Time (within 2% of value) <60 sec <60 sec
Load Resistance 50 (Vs-20) Ohm 50 (Vs-20) Ohm
Physical
Size - Height 4.0 in 101.6 mm
Size - Diameter 0.621 in 15.8 mm
Weight 2.5 oz 71 gm
Housing Material Stainless Steel Stainless Steel
Electrical Connector (#1 ) 2-Pin MIL-C-5015 2-Pin MIL-C-5015
Electrical Connection Position (#1 ) Sensor End Sensor End
Electrical Connections (#1 ) (Pin A) AC IN Pos AC IN Pos
Electrical Connections (#1 ) (Pin B) AC IN Neg AC IN Neg
Electrical Connector (#2 ) 3-Pin MIL-C-5015 3-Pin MIL-C-5015
Electrical Connection Position (#2 ) Output End Output End
Electrical Connections (#2 ) (Pin A) 4-20 mA Pos (+) 4-20 mA Pos (+)
Electrical Connections (#2 ) (Pin B) 4-20 mA Neg & AC OUT Neg 4-20 mA Neg & AC OUT Neg
Electrical Connections (#2 ) (Pin C) AC OUT Pos AC OUT Pos
Sealing Welded Hermetic Welded Hermetic

* All specifications are at room temperature unless otherwise specified.